ConduitCount

How many 350 kcmil THHN fit in 1-1/4" Flex?

1350 kcmil THHN/THWN-2 wires in 1-1/4" Flexible metal conduit (FMC, Greenfield)

1.277 sq in × 53 % = 0.6768 sq in allowed. ÷ 0.5242 sq in per wire = 1.29.

1 350 kcmil THHN in 1-1/4" Flex, drawn to scale

This pull in numbers

1 wires fill
41.0 % of 1-1/4" Flex
Limit for one
53 %
For 2 or more
2-1/2" Flex, up to 3
Pipe to wire diameter
1.56 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

350 kcmil THHN in other 1-1/4" conduit

350 kcmil THHN in other Flex sizes

Other wire sizes in 1-1/4" Flex

Charts