Derating for more than three wires

Fill tells you how many wires fit. Derating tells you what each may carry once they're in there. With more than three current-carrying conductors in one raceway, their ampacity is adjusted by Table 310.15(C)(1).

Current-carrying conductorsPercent of Table 310.16
4 to 680 %
7 to 970 %
10 to 2050 %
21 to 3045 %
31 to 4040 %
41 and above35 %

What counts as current-carrying

  • Every ungrounded (hot) conductor.
  • A neutral that carries only the unbalanced current of its circuit doesn't count (310.15(E)). On a 4-wire wye with mostly nonlinear loads, it does.
  • Equipment grounds never count.

THHN copper, adjusted

THHN's 90 °C ampacity is the starting point for derating; the result still can't exceed what the terminals allow (usually the 75 °C column) or the small-conductor limits of 240.4(D).

Size90 °C4-67-910-2021-3031-4041+
#14252017.512.511.3108.8
#123024211513.51210.5
#1040322820181614
#8554438.527.524.82219.3
#6756052.537.533.83026.3
#4957666.547.542.83833.3
#31159280.557.551.84640.3
#2130104916558.55245.5
#1145116101.572.565.35850.8
#1/01701361198576.56859.5
#2/0195156136.597.587.87868.3
#3/0225180157.5112.5101.39078.8
#4/026020818213011710491

Amps, 30 °C ambient. Other ambient temperatures take the correction factors of 310.15(B) as well.