ConduitCount

How many 3/0 AWG XHHW-2 fit in conduit

3/0 AWG XHHW-2 is about 0.580 in across and 0.2642 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
3/4"11110111
1"11111111
1-1/4"11111111
1-1/2"33332333
2"55554555
2-1/2"9777677
3"1312111191011
3-1/2"17161514131414
4"22201919171919
5"303027
6"444338

Empty cells: that type isn't made in that size.

Other sizes of XHHW-2

The same size in other insulation