How many 3 AWG XHHW-2 fit in conduit

3 AWG XHHW-2 is about 0.350 in across and 0.0962 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
3/8"01
1/2"11111111
3/4"11111111
1"34333333
1-1/4"67665566
1-1/2"89887788
2"1415141312131313
2-1/2"24212019172020
3"36333130262931
3-1/2"48444140364040
4"61565352475252
5"848274
6"121118106

Empty cells: that type isn't made in that size.

Other sizes of XHHW-2

The same size in other insulation