ConduitCount

How many 14 AWG XHHW-2 fit in conduit

14 AWG XHHW-2 is about 0.133 in across and 0.0139 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
3/8"35
1/2"810986998
3/4"1517151411151514
1"2527252419232524
1-1/4"4347444235364442
1-1/2"5864595749535757
2"96104989482949394
2-1/2"168147140135118141140
3"254228215209185203215
3-1/2"332304288280250277280
4"424392370361324361365
5"581568514
6"839822736

Empty cells: that type isn't made in that size.

Other sizes of XHHW-2

The same size in other insulation