ConduitCount

1/2" ENT conduit fill

1/2" Electrical nonmetallic tubing (smurf tube) has an inside area of 0.285 sq in (0.602 in across). Three or more wires may take 40 % of it: 0.1140 sq in.

One wire, 53 %
0.1510 sq in
Two wires, 31 %
0.0883 sq in
Three or more, 40 %
0.1140 sq in
Nipple, 60 %
0.1710 sq in
8 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1/2" ENT

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG1188
12 AWG866
10 AWG544
8 AWG322
6 AWG111
4 AWG111
3 AWG111
2 AWG111

Other 1/2" conduit

ConduitInside area#14#12#10#8#6
Electrical nonmetallic tubing (smurf tube)0.285118531
Electrical metallic tubing0.304129531
Intermediate metal conduit0.3421410632
Rigid metal conduit (RMC, GRC)0.314139631
Rigid PVC conduit, Schedule 400.285118531
Rigid PVC conduit, Schedule 800.21796411
Flexible metal conduit (FMC, Greenfield)0.317139631
Liquidtight flexible metal conduit (LFMC)0.314139631

About ENT

ENT (smurf tube) is the flexible blue tubing used inside walls and slabs, sold in coils rather than sticks. See strap spacing and the fill rules.