3/4" ENT conduit fill
3/4" Electrical nonmetallic tubing (smurf tube) has an inside area of 0.508 sq in (0.804 in across). Three or more wires may take 40 % of it: 0.2032 sq in.
- One wire, 53 %
- 0.2692 sq in
- Two wires, 31 %
- 0.1575 sq in
- Three or more, 40 %
- 0.2032 sq in
- Nipple, 60 %
- 0.3048 sq in
How many wires fit in 3/4" ENT
All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.
| Wire size | THHN/THWN-2 | XHHW-2 | THW/THW-2 |
|---|---|---|---|
| 14 AWG | 21 | 14 | 14 |
| 12 AWG | 15 | 11 | 11 |
| 10 AWG | 9 | 8 | 8 |
| 8 AWG | 5 | 4 | 4 |
| 6 AWG | 4 | 3 | 2 |
| 4 AWG | 1 | 1 | 1 |
| 3 AWG | 1 | 1 | 1 |
| 2 AWG | 1 | 1 | 1 |
| 1 AWG | 1 | 1 | 1 |
| 1/0 AWG | 1 | 1 | 1 |
| 2/0 AWG | 1 | 1 | 1 |
| 3/0 AWG | 1 | 1 | 0 |
Other 3/4" conduit
| Conduit | Inside area | #14 | #12 | #10 | #8 | #6 |
|---|---|---|---|---|---|---|
| Electrical nonmetallic tubing (smurf tube) | 0.508 | 21 | 15 | 9 | 5 | 4 |
| Electrical metallic tubing | 0.533 | 22 | 16 | 10 | 6 | 4 |
| Intermediate metal conduit | 0.586 | 24 | 17 | 11 | 6 | 4 |
| Rigid metal conduit (RMC, GRC) | 0.549 | 22 | 16 | 10 | 6 | 4 |
| Rigid PVC conduit, Schedule 40 | 0.508 | 21 | 15 | 9 | 5 | 4 |
| Rigid PVC conduit, Schedule 80 | 0.409 | 17 | 12 | 7 | 4 | 3 |
| Flexible metal conduit (FMC, Greenfield) | 0.533 | 22 | 16 | 10 | 6 | 4 |
| Liquidtight flexible metal conduit (LFMC) | 0.541 | 22 | 16 | 10 | 6 | 4 |
About ENT
ENT (smurf tube) is the flexible blue tubing used inside walls and slabs, sold in coils rather than sticks. See strap spacing and the fill rules.