1/2" Rigid conduit fill

1/2" Rigid metal conduit (RMC, GRC) has an inside area of 0.314 sq in (0.632 in across). Three or more wires may take 40 % of it: 0.1256 sq in.

One wire, 53 %
0.1664 sq in
Two wires, 31 %
0.0973 sq in
Three or more, 40 %
0.1256 sq in
Nipple, 60 %
0.1884 sq in
Support
Every 10 ft, 3 ft from boxes
Sold in
10 ft sticks
9 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1/2" Rigid

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG1399
12 AWG977
10 AWG655
8 AWG333
6 AWG111
4 AWG111
3 AWG111
2 AWG111
1 AWG110

Other 1/2" conduit

About Rigid

Rigid (galvanized rigid conduit, GRC) has the thickest wall and the least room inside of the steel types. Support follows 344.30: within 3 ft of each box, then every 10 ft, or longer on straight runs with threaded couplings (Table 344.30(B)(2)). See strap spacing and the fill rules.