ConduitCount

1/2" PVC Sch 80 conduit fill

1/2" Rigid PVC conduit, Schedule 80 has an inside area of 0.217 sq in (0.526 in across). Three or more wires may take 40 % of it: 0.0868 sq in.

One wire, 53 %
0.1150 sq in
Two wires, 31 %
0.0673 sq in
Three or more, 40 %
0.0868 sq in
Nipple, 60 %
0.1302 sq in
Support
Every 3 ft, 3 ft from boxes
Sold in
10 ft sticks
6 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1/2" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG966
12 AWG644
10 AWG433
8 AWG111
6 AWG111
4 AWG111
3 AWG111
2 AWG010

Other 1/2" conduit

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.