ConduitCount

3/4" PVC Sch 40 conduit fill

3/4" Rigid PVC conduit, Schedule 40 has an inside area of 0.508 sq in (0.804 in across). Three or more wires may take 40 % of it: 0.2032 sq in.

One wire, 53 %
0.2692 sq in
Two wires, 31 %
0.1575 sq in
Three or more, 40 %
0.2032 sq in
Nipple, 60 %
0.3048 sq in
Support
Every 3 ft, 3 ft from boxes
Sold in
10 ft sticks
15 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 3/4" PVC Sch 40

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG211414
12 AWG151111
10 AWG988
8 AWG544
6 AWG432
4 AWG111
3 AWG111
2 AWG111
1 AWG111
1/0 AWG111
2/0 AWG111
3/0 AWG110

Other 3/4" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 400.5082115954
Electrical metallic tubing0.53322161064
Intermediate metal conduit0.58624171164
Rigid metal conduit (RMC, GRC)0.54922161064
Rigid PVC conduit, Schedule 800.4091712743
Flexible metal conduit (FMC, Greenfield)0.53322161064
Liquidtight flexible metal conduit (LFMC)0.54122161064
Electrical nonmetallic tubing (smurf tube)0.5082115954

About PVC Sch 40

Schedule 40 is the standard PVC wall. Support spacing gets wider as the size goes up (Table 352.30), and long runs in the sun need expansion fittings (352.44). See strap spacing and the fill rules.