3/4" Liquidtight conduit fill
3/4" Liquidtight flexible metal conduit (LFMC) has an inside area of 0.541 sq in (0.830 in across). Three or more wires may take 40 % of it: 0.2164 sq in.
- One wire, 53 %
- 0.2867 sq in
- Two wires, 31 %
- 0.1677 sq in
- Three or more, 40 %
- 0.2164 sq in
- Nipple, 60 %
- 0.3246 sq in
- Support
- Every 4.5 ft, 12 in from boxes
How many wires fit in 3/4" Liquidtight
All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.
| Wire size | THHN/THWN-2 | XHHW-2 | THW/THW-2 |
|---|---|---|---|
| 14 AWG | 22 | 15 | 15 |
| 12 AWG | 16 | 12 | 12 |
| 10 AWG | 10 | 9 | 9 |
| 8 AWG | 6 | 5 | 5 |
| 6 AWG | 4 | 3 | 3 |
| 4 AWG | 2 | 2 | 1 |
| 3 AWG | 1 | 1 | 1 |
| 2 AWG | 1 | 1 | 1 |
| 1 AWG | 1 | 1 | 1 |
| 1/0 AWG | 1 | 1 | 1 |
| 2/0 AWG | 1 | 1 | 1 |
| 3/0 AWG | 1 | 1 | 0 |
Other 3/4" conduit
| Conduit | Inside area | #14 | #12 | #10 | #8 | #6 |
|---|---|---|---|---|---|---|
| Liquidtight flexible metal conduit (LFMC) | 0.541 | 22 | 16 | 10 | 6 | 4 |
| Electrical metallic tubing | 0.533 | 22 | 16 | 10 | 6 | 4 |
| Intermediate metal conduit | 0.586 | 24 | 17 | 11 | 6 | 4 |
| Rigid metal conduit (RMC, GRC) | 0.549 | 22 | 16 | 10 | 6 | 4 |
| Rigid PVC conduit, Schedule 40 | 0.508 | 21 | 15 | 9 | 5 | 4 |
| Rigid PVC conduit, Schedule 80 | 0.409 | 17 | 12 | 7 | 4 | 3 |
| Flexible metal conduit (FMC, Greenfield) | 0.533 | 22 | 16 | 10 | 6 | 4 |
| Electrical nonmetallic tubing (smurf tube) | 0.508 | 21 | 15 | 9 | 5 | 4 |
About Liquidtight
Liquidtight is supported every 4-1/2 ft and within 12 in of each box (350.30), with exceptions for short lengths at equipment. See strap spacing and the fill rules.