ConduitCount

3/4" PVC Sch 80 conduit fill

3/4" Rigid PVC conduit, Schedule 80 has an inside area of 0.409 sq in (0.722 in across). Three or more wires may take 40 % of it: 0.1636 sq in.

One wire, 53 %
0.2168 sq in
Two wires, 31 %
0.1268 sq in
Three or more, 40 %
0.1636 sq in
Nipple, 60 %
0.2454 sq in
Support
Every 3 ft, 3 ft from boxes
Sold in
10 ft sticks
12 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 3/4" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG171111
12 AWG1299
10 AWG766
8 AWG433
6 AWG321
4 AWG111
3 AWG111
2 AWG111
1 AWG111
1/0 AWG110

Other 3/4" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 800.4091712743
Electrical metallic tubing0.53322161064
Intermediate metal conduit0.58624171164
Rigid metal conduit (RMC, GRC)0.54922161064
Rigid PVC conduit, Schedule 400.5082115954
Flexible metal conduit (FMC, Greenfield)0.53322161064
Liquidtight flexible metal conduit (LFMC)0.54122161064
Electrical nonmetallic tubing (smurf tube)0.5082115954

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.