ConduitCount

5" PVC Sch 40 conduit fill

5" Rigid PVC conduit, Schedule 40 has an inside area of 19.761 sq in (5.016 in across). Three or more wires may take 40 % of it: 7.9044 sq in.

One wire, 53 %
10.4733 sq in
Two wires, 31 %
6.1259 sq in
Three or more, 40 %
7.9044 sq in
Nipple, 60 %
11.8566 sq in
Support
Every 7 ft, 3 ft from boxes
Sold in
10 ft sticks
42 #1/0 THHN, the most it may hold, drawn to scale

How many wires fit in 5" PVC Sch 40

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG815568568
12 AWG594436436
10 AWG374325325
8 AWG216181181
6 AWG156134109
4 AWG969781
3 AWG818269
2 AWG686959
1 AWG505141
1/0 AWG424335
2/0 AWG353630
3/0 AWG293025
4/0 AWG242421
250 kcmil202017
300 kcmil171715
350 kcmil151513
400 kcmil131312
500 kcmil111110
600 kcmil998
700 kcmil887
750 kcmil776
800 kcmil776
900 kcmil666
1000 kcmil665

Other 5" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 4019.761815594374216156
Rigid metal conduit (RMC, GRC)20.212833608383221159
Rigid PVC conduit, Schedule 8017.855736537338195141

About PVC Sch 40

Schedule 40 is the standard PVC wall. Support spacing gets wider as the size goes up (Table 352.30), and long runs in the sun need expansion fittings (352.44). See strap spacing and the fill rules.