ConduitCount

How many #6 THHN fit in 5" PVC Sch 40?

1566 AWG THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 40

19.761 sq in × 40 % = 7.9044 sq in allowed. ÷ 0.0507 sq in per wire = 155.91, which Note 7 rounds up to 156 because the decimal is 0.8 or more.

156 #6 THHN in 5" PVC Sch 40, drawn to scale

This pull in numbers

156 wires fill
40.0 % of 5" PVC Sch 40
Limit for three or more
40 %
For 157 or more
6" PVC Sch 40, up to 225
Pipe to wire diameter
19.75 to 1
In THW insulation
109 fit
In XHHW-2 insulation
134 fit

Before you pull 156

#6 THHN in other 5" conduit

ConduitInside areaMost #6 THHN
Rigid metal conduit (RMC, GRC)20.212159
Rigid PVC conduit, Schedule 4019.761156
Rigid PVC conduit, Schedule 8017.855141

#6 THHN in other PVC Sch 40 sizes

Other wire sizes in 5" PVC Sch 40

Charts