How many 500 kcmil THHN fit in 5" PVC Sch 40?

11500 kcmil THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 40

19.761 sq in × 40 % = 7.9044 sq in allowed. ÷ 0.7073 sq in per wire = 11.18, so 11.

11 500 kcmil THHN in 5" PVC Sch 40, drawn to scale

This pull in numbers

11 wires fill
39.4 % of 5" PVC Sch 40
Limit for three or more
40 %
For 12 or more
6" PVC Sch 40, up to 16
Pipe to wire diameter
5.29 to 1
In THW insulation
10 fit
In XHHW-2 insulation
11 fit

Before you pull 11

500 kcmil THHN in other 5" conduit

ConduitInside areaMost 500 kcmil THHN
Rigid metal conduit (RMC, GRC)20.21211
Rigid PVC conduit, Schedule 4019.76111
Rigid PVC conduit, Schedule 8017.85510

500 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 5" PVC Sch 40