6" PVC Sch 40 conduit fill

6" Rigid PVC conduit, Schedule 40 has an inside area of 28.567 sq in (6.031 in across). Three or more wires may take 40 % of it: 11.4268 sq in.

One wire, 53 %
15.1405 sq in
Two wires, 31 %
8.8558 sq in
Three or more, 40 %
11.4268 sq in
Nipple, 60 %
17.1402 sq in
Support
Every 8 ft, 3 ft from boxes
Sold in
10 ft sticks
61 #1/0 THHN, the most it may hold, drawn to scale

How many wires fit in 6" PVC Sch 40

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG1178822822
12 AWG859631631
10 AWG541470470
8 AWG312261261
6 AWG225193157
4 AWG138140117
3 AWG117118100
2 AWG989985
1 AWG737460
1/0 AWG616251
2/0 AWG515243
3/0 AWG424336
4/0 AWG353530
250 kcmil282925
300 kcmil242521
350 kcmil212219
400 kcmil191917
500 kcmil161614
600 kcmil131311
700 kcmil111110
750 kcmil111110
800 kcmil10109
900 kcmil998
1000 kcmil887

Other 6" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 4028.5671178859541312225
Rigid metal conduit (RMC, GRC)29.1581202877552318230
Rigid PVC conduit, Schedule 8025.5981055770485279202

About PVC Sch 40

Schedule 40 is the standard PVC wall. Support spacing gets wider as the size goes up (Table 352.30), and long runs in the sun need expansion fittings (352.44). See strap spacing and the fill rules.