ConduitCount

1" PVC Sch 80 conduit fill

1" Rigid PVC conduit, Schedule 80 has an inside area of 0.688 sq in (0.936 in across). Three or more wires may take 40 % of it: 0.2752 sq in.

One wire, 53 %
0.3646 sq in
Two wires, 31 %
0.2133 sq in
Three or more, 40 %
0.2752 sq in
Nipple, 60 %
0.4128 sq in
Support
Every 3 ft, 3 ft from boxes
Sold in
10 ft sticks
20 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG281919
12 AWG201515
10 AWG131111
8 AWG766
6 AWG543
4 AWG333
3 AWG331
2 AWG111
1 AWG111
1/0 AWG111
2/0 AWG111
3/0 AWG111
4/0 AWG110

Other 1" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 800.68828201375
Electrical metallic tubing0.86435261697
Intermediate metal conduit0.959392918107
Rigid metal conduit (RMC, GRC)0.88736261797
Rigid PVC conduit, Schedule 400.83234251596
Flexible metal conduit (FMC, Greenfield)0.81733241596
Liquidtight flexible metal conduit (LFMC)0.87336261697
Electrical nonmetallic tubing (smurf tube)0.83234251596

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.