How many #4 THHN fit in 1" PVC Sch 80?

34 AWG THHN/THWN-2 wires in 1" Rigid PVC conduit, Schedule 80

0.688 sq in × 40 % = 0.2752 sq in allowed. ÷ 0.0824 sq in per wire = 3.34, so 3.

3 #4 THHN in 1" PVC Sch 80, drawn to scale

This pull in numbers

3 wires fill
35.9 % of 1" PVC Sch 80
Limit for three or more
40 %
For 4 or more
1-1/4" PVC Sch 80, up to 6
Pipe to wire diameter
2.89 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.89 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.