1-1/4" Rigid PVC conduit, Schedule 80 has an inside area of 1.237 sq in (1.255 in across). Three or more wires may take 40 % of it: 0.4948 sq in.

One wire, 53 %
0.6556 sq in
Two wires, 31 %
0.3835 sq in
Three or more, 40 %
0.4948 sq in
Nipple, 60 %
0.7422 sq in
Support
Every 5 ft, 3 ft from boxes
Sold in
10 ft sticks
37 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1-1/4" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG513535
12 AWG372727
10 AWG232020
8 AWG131111
6 AWG987
4 AWG665
3 AWG554
2 AWG443
1 AWG332
1/0 AWG221
2/0 AWG111
3/0 AWG111
4/0 AWG111
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil110

Other 1-1/4" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 801.237513723139
Electrical metallic tubing1.4966145281612
Intermediate metal conduit1.6476849311813
Rigid metal conduit (RMC, GRC)1.5266346291612
Rigid PVC conduit, Schedule 401.4536043271611
Flexible metal conduit (FMC, Greenfield)1.2775238241410
Liquidtight flexible metal conduit (LFMC)1.5286346291612
Electrical nonmetallic tubing (smurf tube)1.4536043271611

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.