How many #2/0 THHN fit in 1-1/2" Flex?
32/0 AWG THHN/THWN-2 wires in 1-1/2" Flexible metal conduit (FMC, Greenfield)
1.858 sq in × 40 % = 0.7432 sq in allowed. ÷ 0.2223 sq in per wire = 3.34, so 3.
This pull in numbers
- 3 wires fill
- 35.9 % of 1-1/2" Flex
- Limit for three or more
- 40 %
- For 4 or more
- 2" Flex, up to 6
- Pipe to wire diameter
- 2.89 to 1
- In THW insulation
- 3 fit
- In XHHW-2 insulation
- 3 fit
The pipe is 2.89 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.
Before you pull 3
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 3 is the total, not the hots.
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#2/0 THHN in other 1-1/2" conduit
| Conduit | Inside area | Most #2/0 THHN |
|---|---|---|
| Electrical metallic tubing | 2.036 | 3 |
| Intermediate metal conduit | 2.225 | 4 |
| Rigid metal conduit (RMC, GRC) | 2.071 | 3 |
| Rigid PVC conduit, Schedule 40 | 1.986 | 3 |
| Rigid PVC conduit, Schedule 80 | 1.711 | 3 |
| Flexible metal conduit (FMC, Greenfield) | 1.858 | 3 |
| Liquidtight flexible metal conduit (LFMC) | 1.981 | 3 |
| Electrical nonmetallic tubing (smurf tube) | 1.986 | 3 |
#2/0 THHN in other Flex sizes
Other wire sizes in 1-1/2" Flex
#14: 76#12: 56#10: 35#8: 20#6: 14#4: 9#3: 7#2: 6#1: 4#1/0: 4#2/0: 3#3/0: 2#4/0: 1250 kcmil: 1300 kcmil: 1350 kcmil: 1500 kcmil: 1