How many #2/0 THHN fit in 1-1/2" PVC Sch 80?

32/0 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80

1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.2223 sq in per wire = 3.08, so 3.

3 #2/0 THHN in 1-1/2" PVC Sch 80, drawn to scale

This pull in numbers

3 wires fill
39.0 % of 1-1/2" PVC Sch 80
Limit for three or more
40 %
For 4 or more
2" PVC Sch 80, up to 5
Pipe to wire diameter
2.77 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

Before you pull 3

#2/0 THHN in other 1-1/2" conduit

#2/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/2" PVC Sch 80