How many #2/0 THHN fit in 3-1/2" Flex?

172/0 AWG THHN/THWN-2 wires in 3-1/2" Flexible metal conduit (FMC, Greenfield)

9.621 sq in × 40 % = 3.8484 sq in allowed. ÷ 0.2223 sq in per wire = 17.31, so 17.

17 #2/0 THHN in 3-1/2" Flex, drawn to scale

This pull in numbers

17 wires fill
39.3 % of 3-1/2" Flex
Limit for three or more
40 %
For 18 or more
4" Flex, up to 22
Pipe to wire diameter
6.58 to 1
In THW insulation
14 fit
In XHHW-2 insulation
17 fit

Before you pull 17

#2/0 THHN in other 3-1/2" conduit

ConduitInside areaMost #2/0 THHN
Electrical metallic tubing11.54520
Intermediate metal conduit10.58419
Rigid metal conduit (RMC, GRC)10.01018
Rigid PVC conduit, Schedule 409.73717
Rigid PVC conduit, Schedule 808.68815
Flexible metal conduit (FMC, Greenfield)9.62117
Liquidtight flexible metal conduit (LFMC)9.73117

#2/0 THHN in other Flex sizes

Other wire sizes in 3-1/2" Flex

Charts