ConduitCount

How many #2/0 THHN fit in 1-1/2" ENT?

32/0 AWG THHN/THWN-2 wires in 1-1/2" Electrical nonmetallic tubing (smurf tube)

1.986 sq in × 40 % = 0.7944 sq in allowed. ÷ 0.2223 sq in per wire = 3.57, so 3.

3 #2/0 THHN in 1-1/2" ENT, drawn to scale

This pull in numbers

3 wires fill
33.6 % of 1-1/2" ENT
Limit for three or more
40 %
For 4 or more
2" ENT, up to 6
Pipe to wire diameter
2.99 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.99 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

#2/0 THHN in other 1-1/2" conduit

#2/0 THHN in other ENT sizes

Other wire sizes in 1-1/2" ENT

Charts