ConduitCount

How many 250 kcmil THHN fit in 1-1/4" Liquidtight?

1250 kcmil THHN/THWN-2 wires in 1-1/4" Liquidtight flexible metal conduit (LFMC)

1.528 sq in × 53 % = 0.8098 sq in allowed. ÷ 0.3970 sq in per wire = 2.04.

1 250 kcmil THHN in 1-1/4" Liquidtight, drawn to scale

This pull in numbers

1 wires fill
26.0 % of 1-1/4" Liquidtight
Limit for one
53 %
For 2 or more
2" Liquidtight, up to 3
Pipe to wire diameter
1.96 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

250 kcmil THHN in other 1-1/4" conduit

250 kcmil THHN in other Liquidtight sizes

Other wire sizes in 1-1/4" Liquidtight

Charts