ConduitCount

How many #8 THHN fit in 1-1/4" Liquidtight?

168 AWG THHN/THWN-2 wires in 1-1/4" Liquidtight flexible metal conduit (LFMC)

1.528 sq in × 40 % = 0.6112 sq in allowed. ÷ 0.0366 sq in per wire = 16.70, so 16.

16 #8 THHN in 1-1/4" Liquidtight, drawn to scale

This pull in numbers

16 wires fill
38.3 % of 1-1/4" Liquidtight
Limit for three or more
40 %
For 17 or more
1-1/2" Liquidtight, up to 21
Pipe to wire diameter
6.46 to 1
In THW insulation
14 fit
In XHHW-2 insulation
14 fit

Before you pull 16

#8 THHN in other 1-1/4" conduit

#8 THHN in other Liquidtight sizes

Other wire sizes in 1-1/4" Liquidtight

Charts