How many 250 kcmil THHN fit in 2" Liquidtight?
3250 kcmil THHN/THWN-2 wires in 2" Liquidtight flexible metal conduit (LFMC)
3.246 sq in × 40 % = 1.2984 sq in allowed. ÷ 0.3970 sq in per wire = 3.27, so 3.
This pull in numbers
- 3 wires fill
- 36.7 % of 2" Liquidtight
- Limit for three or more
- 40 %
- For 4 or more
- 2-1/2" Liquidtight, up to 5
- Pipe to wire diameter
- 2.86 to 1
- In THW insulation
- 3 fit
- In XHHW-2 insulation
- 3 fit
The pipe is 2.86 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.
Before you pull 3
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 3 is the total, not the hots.
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
250 kcmil THHN in other 2" conduit
| Conduit | Inside area | Most 250 kcmil THHN |
|---|---|---|
| Electrical metallic tubing | 3.356 | 3 |
| Intermediate metal conduit | 3.630 | 3 |
| Rigid metal conduit (RMC, GRC) | 3.408 | 3 |
| Rigid PVC conduit, Schedule 40 | 3.291 | 3 |
| Rigid PVC conduit, Schedule 80 | 2.874 | 3 |
| Flexible metal conduit (FMC, Greenfield) | 3.269 | 3 |
| Liquidtight flexible metal conduit (LFMC) | 3.246 | 3 |
| Electrical nonmetallic tubing (smurf tube) | 3.291 | 3 |
250 kcmil THHN in other Liquidtight sizes
Other wire sizes in 2" Liquidtight
#14: 134#12: 97#10: 61#8: 35#6: 25#4: 15#3: 13#2: 11#1: 8#1/0: 7#2/0: 6#3/0: 5#4/0: 4250 kcmil: 3300 kcmil: 3350 kcmil: 1500 kcmil: 1