ConduitCount

How many 12 AWG THW/THW-2 fit in conduit

12 AWG THW/THW-2 is about 0.152 in across and 0.0181 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
3/8"14
1/2"67764776
3/4"111312119111211
1"1921191815181918
1-1/4"3336333227283332
1-1/2"4549454438414344
2"7480757263727172
2-1/2"12911310710391108108
3"195175165160142156165
3-1/2"255234221215192212215
4"326301284277248277280
5"446436394
6"644631565

Empty cells: that type isn't made in that size.

Other sizes of THW/THW-2

The same size in other insulation