ConduitCount

How many 6 AWG THW/THW-2 fit in conduit

6 AWG THW/THW-2 is about 0.304 in across and 0.0726 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
3/8"01
1/2"11111111
3/4"33321332
1"45543454
1-1/4"89887788
1-1/2"111211119101111
2"1820181816181818
2-1/2"32282726222727
3"48434140353941
3-1/2"63585553485353
4"81757169626970
5"11110998
6"160157141

Empty cells: that type isn't made in that size.

Other sizes of THW/THW-2