How many 14 AWG THHN/THWN-2 fit in conduit

14 AWG THHN/THWN-2 is about 0.111 in across and 0.0097 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
3/8"48
1/2"121413119131311
3/4"2224222117222221
1"3539363428333634
1-1/4"6168636051526360
1-1/2"8491858270768182
2"138149140135118135134135
2-1/2"241211200193170202201
3"364326309299265291308
3-1/2"476436412401358396401
4"608562531517464518523
5"833815736
6"120211781055

Empty cells: that type isn't made in that size.