1612 AWG THHN/THWN-2 wires in 3/4" Liquidtight flexible metal conduit (LFMC)

0.541 sq in × 40 % = 0.2164 sq in allowed. ÷ 0.0133 sq in per wire = 16.27, so 16.

16 #12 THHN in 3/4" Liquidtight, drawn to scale

This pull in numbers

16 wires fill
39.3 % of 3/4" Liquidtight
Limit for three or more
40 %
For 17 or more
1" Liquidtight, up to 26
Pipe to wire diameter
6.38 to 1
In THW insulation
12 fit
In XHHW-2 insulation