ConduitCount

How many #8 THHN fit in 1/2" Rigid?

38 AWG THHN/THWN-2 wires in 1/2" Rigid metal conduit (RMC, GRC)

0.314 sq in × 40 % = 0.1256 sq in allowed. ÷ 0.0366 sq in per wire = 3.43, so 3.

3 #8 THHN in 1/2" Rigid, drawn to scale

This pull in numbers

3 wires fill
35.0 % of 1/2" Rigid
Limit for three or more
40 %
For 4 or more
3/4" Rigid, up to 6
Pipe to wire diameter
2.93 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.93 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

#8 THHN in other 1/2" conduit

#8 THHN in other Rigid sizes

Other wire sizes in 1/2" Rigid

Charts