Rigid metal conduit (RMC, GRC) fill chart

The most THHN wires of one size each Rigid size may hold, with three or more wires at 40 % fill. Pick a size for XHHW-2 and THW as well.

Trade sizeInside area40 %#14#12#10#8#6#4#2#1/0#4/0250 kcmil500 kcmil
1/2"0.3140.126139631110000
3/4"0.5490.22022161064211000
1"0.8870.35536261797431110
1-1/4"1.5260.6106346291612753111
1-1/2"2.0710.82885623922161074111
2"3.4081.36314010264372716117431
2-1/2"4.8661.946200146925338231710652
3"7.4993.0003092251428259362616974
3-1/2"10.0104.0044123011891097948342112105
4"12.8825.15353138724414010162442716137
5"20.2128.085833608383221159987043252011
6"29.15811.663120287755231823014110063362916

Areas in square inches, from Chapter 9, Table 4 (2023 NEC). THHN/THWN-2 areas from Table 5.

About Rigid

Rigid (galvanized rigid conduit, GRC) has the thickest wall and the least room inside of the steel types. Support follows 344.30: within 3 ft of each box, then every 10 ft, or longer on straight runs with threaded couplings (Table 344.30(B)(2)). See strap spacing and the fill rules.