ConduitCount

How many #12 THHN fit in 1/2" Liquidtight?

912 AWG THHN/THWN-2 wires in 1/2" Liquidtight flexible metal conduit (LFMC)

0.314 sq in × 40 % = 0.1256 sq in allowed. ÷ 0.0133 sq in per wire = 9.44, so 9.

9 #12 THHN in 1/2" Liquidtight, drawn to scale

This pull in numbers

9 wires fill
38.1 % of 1/2" Liquidtight
Limit for three or more
40 %
For 10 or more
3/4" Liquidtight, up to 16
Pipe to wire diameter
4.86 to 1
In THW insulation
7 fit
In XHHW-2 insulation
7 fit

Before you pull 9

#12 THHN in other 1/2" conduit

#12 THHN in other Liquidtight sizes

Other wire sizes in 1/2" Liquidtight

Charts