How many #12 THHN fit in 1/2" IMC?

1012 AWG THHN/THWN-2 wires in 1/2" Intermediate metal conduit

0.342 sq in × 40 % = 0.1368 sq in allowed. ÷ 0.0133 sq in per wire = 10.29, so 10.

10 #12 THHN in 1/2" IMC, drawn to scale

This pull in numbers

10 wires fill
38.9 % of 1/2" IMC
Limit for three or more
40 %
For 11 or more
3/4" IMC, up to 17
Pipe to wire diameter
5.08 to 1
In THW insulation
7 fit
In XHHW-2 insulation
7 fit

Before you pull 10

#12 THHN in other 1/2" conduit

#12 THHN in other IMC sizes

Other wire sizes in 1/2" IMC