ConduitCount

How many #14 THHN fit in 1/2" Liquidtight?

1314 AWG THHN/THWN-2 wires in 1/2" Liquidtight flexible metal conduit (LFMC)

0.314 sq in × 40 % = 0.1256 sq in allowed. ÷ 0.0097 sq in per wire = 12.95, which Note 7 rounds up to 13 because the decimal is 0.8 or more.

13 #14 THHN in 1/2" Liquidtight, drawn to scale

This pull in numbers

13 wires fill
40.2 % of 1/2" Liquidtight
Limit for three or more
40 %
For 14 or more
3/4" Liquidtight, up to 22
Pipe to wire diameter
5.69 to 1
In THW insulation
9 fit
In XHHW-2 insulation
9 fit

Before you pull 13

#14 THHN in other 1/2" conduit

#14 THHN in other Liquidtight sizes

Other wire sizes in 1/2" Liquidtight

Charts