ConduitCount

How many #4/0 THHN fit in 1-1/2" ENT?

14/0 AWG THHN/THWN-2 wires in 1-1/2" Electrical nonmetallic tubing (smurf tube)

1.986 sq in × 53 % = 1.0526 sq in allowed. ÷ 0.3237 sq in per wire = 3.25.

1 #4/0 THHN in 1-1/2" ENT, drawn to scale

This pull in numbers

1 wires fill
16.3 % of 1-1/2" ENT
Limit for one
53 %
For 2 or more
2" ENT, up to 4
Pipe to wire diameter
2.48 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#4/0 THHN in other 1-1/2" conduit

#4/0 THHN in other ENT sizes

Other wire sizes in 1-1/2" ENT

Charts