ConduitCount

How many #6 THHN fit in 1-1/2" ENT?

156 AWG THHN/THWN-2 wires in 1-1/2" Electrical nonmetallic tubing (smurf tube)

1.986 sq in × 40 % = 0.7944 sq in allowed. ÷ 0.0507 sq in per wire = 15.67, so 15.

15 #6 THHN in 1-1/2" ENT, drawn to scale

This pull in numbers

15 wires fill
38.3 % of 1-1/2" ENT
Limit for three or more
40 %
For 16 or more
2" ENT, up to 26
Pipe to wire diameter
6.26 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 15

#6 THHN in other 1-1/2" conduit

#6 THHN in other ENT sizes

Other wire sizes in 1-1/2" ENT

Charts