32 AWG THHN/THWN-2 wires in 1" Electrical nonmetallic tubing (smurf tube)

0.832 sq in × 40 % = 0.3328 sq in allowed. ÷ 0.1158 sq in per wire = 2.87, which Note 7 rounds up to 3 because the decimal is 0.8 or more.

3 #2 THHN in 1" ENT, drawn to scale

This pull in numbers

3 wires fill
41.8 % of 1" ENT
Limit for three or more
40 %
For 4 or more
1-1/4" ENT, up to 5
Pipe to wire diameter
2.68 to 1
In THW insulation
1 fit
In XHHW-2 insulation
3 fit

Before you pull 3

#2 THHN in other 1" conduit

#2 THHN in other ENT sizes