ConduitCount

How many #6 THHN fit in 1" ENT?

66 AWG THHN/THWN-2 wires in 1" Electrical nonmetallic tubing (smurf tube)

0.832 sq in × 40 % = 0.3328 sq in allowed. ÷ 0.0507 sq in per wire = 6.56, so 6.

6 #6 THHN in 1" ENT, drawn to scale

This pull in numbers

6 wires fill
36.6 % of 1" ENT
Limit for three or more
40 %
For 7 or more
1-1/4" ENT, up to 11
Pipe to wire diameter
4.05 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 6

#6 THHN in other 1" conduit

#6 THHN in other ENT sizes

Other wire sizes in 1" ENT

Charts