ConduitCount

How many 2 AWG THHN/THWN-2 fit in conduit

2 AWG THHN/THWN-2 is about 0.384 in across and 0.1158 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
1/2"11110111
3/4"11111111
1"33331333
1-1/4"55554455
1-1/2"77776677
2"1112111110111111
2-1/2"20171716141717
3"30272625222426
3-1/2"40363433303333
4"51474443394344
5"706861
6"1009888

Empty cells: that type isn't made in that size.

Other sizes of THHN/THWN-2

The same size in other insulation