ConduitCount

How many #2 THHN fit in 1" IMC?

32 AWG THHN/THWN-2 wires in 1" Intermediate metal conduit

0.959 sq in × 40 % = 0.3836 sq in allowed. ÷ 0.1158 sq in per wire = 3.31, so 3.

3 #2 THHN in 1" IMC, drawn to scale

This pull in numbers

3 wires fill
36.2 % of 1" IMC
Limit for three or more
40 %
For 4 or more
1-1/4" IMC, up to 5
Pipe to wire diameter
2.88 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.88 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

#2 THHN in other 1" conduit

#2 THHN in other IMC sizes

Other wire sizes in 1" IMC

Charts