How many #10 THHN fit in 1" ENT?
1510 AWG THHN/THWN-2 wires in 1" Electrical nonmetallic tubing (smurf tube)
0.832 sq in × 40 % = 0.3328 sq in allowed. ÷ 0.0211 sq in per wire = 15.77, so 15.
This pull in numbers
- 15 wires fill
- 38.0 % of 1" ENT
- Limit for three or more
- 40 %
- For 16 or more
- 1-1/4" ENT, up to 27
- Pipe to wire diameter
- 6.27 to 1
- In THW insulation
- 13 fit
- In XHHW-2 insulation
- 13 fit
Before you pull 15
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 15 is the total, not the hots.
- Derating. If all 15 were current-carrying, each would be adjusted to 50 % of its ampacity (Table 310.15(C)(1)): a #10 THHN at 40 A in the 90 °C column becomes 20 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#10 THHN in other 1" conduit
| Conduit | Inside area | Most #10 THHN |
|---|---|---|
| Electrical metallic tubing | 0.864 | 16 |
| Intermediate metal conduit | 0.959 | 18 |
| Rigid metal conduit (RMC, GRC) | 0.887 | 17 |
| Rigid PVC conduit, Schedule 40 | 0.832 | 15 |
| Rigid PVC conduit, Schedule 80 | 0.688 | 13 |
| Flexible metal conduit (FMC, Greenfield) | 0.817 | 15 |
| Liquidtight flexible metal conduit (LFMC) | 0.873 | 16 |
| Electrical nonmetallic tubing (smurf tube) | 0.832 | 15 |