ConduitCount

How many #3/0 THHN fit in 3" Flex?

103/0 AWG THHN/THWN-2 wires in 3" Flexible metal conduit (FMC, Greenfield)

7.069 sq in × 40 % = 2.8276 sq in allowed. ÷ 0.2679 sq in per wire = 10.55, so 10.

10 #3/0 THHN in 3" Flex, drawn to scale

This pull in numbers

10 wires fill
37.9 % of 3" Flex
Limit for three or more
40 %
For 11 or more
3-1/2" Flex, up to 14
Pipe to wire diameter
5.14 to 1
In THW insulation
9 fit
In XHHW-2 insulation
10 fit

Before you pull 10

#3/0 THHN in other 3" conduit

ConduitInside areaMost #3/0 THHN
Electrical metallic tubing8.84613
Intermediate metal conduit7.92212
Rigid metal conduit (RMC, GRC)7.49911
Rigid PVC conduit, Schedule 407.26811
Rigid PVC conduit, Schedule 806.4429
Flexible metal conduit (FMC, Greenfield)7.06910
Liquidtight flexible metal conduit (LFMC)7.47511

#3/0 THHN in other Flex sizes

Other wire sizes in 3" Flex

Charts