ConduitCount

How many #1/0 THHN fit in 3" Flex?

151/0 AWG THHN/THWN-2 wires in 3" Flexible metal conduit (FMC, Greenfield)

7.069 sq in × 40 % = 2.8276 sq in allowed. ÷ 0.1855 sq in per wire = 15.24, so 15.

15 #1/0 THHN in 3" Flex, drawn to scale

This pull in numbers

15 wires fill
39.4 % of 3" Flex
Limit for three or more
40 %
For 16 or more
3-1/2" Flex, up to 20
Pipe to wire diameter
6.17 to 1
In THW insulation
12 fit
In XHHW-2 insulation
15 fit

Before you pull 15

#1/0 THHN in other 3" conduit

ConduitInside areaMost #1/0 THHN
Electrical metallic tubing8.84619
Intermediate metal conduit7.92217
Rigid metal conduit (RMC, GRC)7.49916
Rigid PVC conduit, Schedule 407.26815
Rigid PVC conduit, Schedule 806.44214
Flexible metal conduit (FMC, Greenfield)7.06915
Liquidtight flexible metal conduit (LFMC)7.47516

#1/0 THHN in other Flex sizes

Other wire sizes in 3" Flex

Charts