ConduitCount

How many #3/0 THHN fit in 3" PVC Sch 80?

93/0 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80

6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.2679 sq in per wire = 9.62, so 9.

9 #3/0 THHN in 3" PVC Sch 80, drawn to scale

This pull in numbers

9 wires fill
37.4 % of 3" PVC Sch 80
Limit for three or more
40 %
For 10 or more
3-1/2" PVC Sch 80, up to 13
Pipe to wire diameter
4.90 to 1
In THW insulation
8 fit
In XHHW-2 insulation
9 fit

Before you pull 9

#3/0 THHN in other 3" conduit

#3/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 3" PVC Sch 80

Charts