ConduitCount

How many #3/0 THHN fit in 4" Flex?

183/0 AWG THHN/THWN-2 wires in 4" Flexible metal conduit (FMC, Greenfield)

12.566 sq in × 40 % = 5.0264 sq in allowed. ÷ 0.2679 sq in per wire = 18.76, so 18.

18 #3/0 THHN in 4" Flex, drawn to scale

This pull in numbers

18 wires fill
38.4 % of 4" Flex
Limit for three or more
40 %
For 19 or more
no bigger Flex
Pipe to wire diameter
6.85 to 1
In THW insulation
16 fit
In XHHW-2 insulation
19 fit

Before you pull 18

#3/0 THHN in other 4" conduit

ConduitInside areaMost #3/0 THHN
Electrical metallic tubing14.75322
Intermediate metal conduit13.63120
Rigid metal conduit (RMC, GRC)12.88219
Rigid PVC conduit, Schedule 4012.55418
Rigid PVC conduit, Schedule 8011.25817
Flexible metal conduit (FMC, Greenfield)12.56618
Liquidtight flexible metal conduit (LFMC)12.69219

#3/0 THHN in other Flex sizes

Other wire sizes in 4" Flex

Charts