ConduitCount

How many 500 kcmil THHN fit in 1-1/2" Liquidtight?

1500 kcmil THHN/THWN-2 wires in 1-1/2" Liquidtight flexible metal conduit (LFMC)

1.981 sq in × 53 % = 1.0499 sq in allowed. ÷ 0.7073 sq in per wire = 1.48.

1 500 kcmil THHN in 1-1/2" Liquidtight, drawn to scale

This pull in numbers

1 wires fill
35.7 % of 1-1/2" Liquidtight
Limit for one
53 %
For 2 or more
2-1/2" Liquidtight, up to 2
Pipe to wire diameter
1.67 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

500 kcmil THHN in other 1-1/2" conduit

500 kcmil THHN in other Liquidtight sizes

Other wire sizes in 1-1/2" Liquidtight

Charts