ConduitCount

How many #10 THHN fit in 1-1/2" Liquidtight?

3710 AWG THHN/THWN-2 wires in 1-1/2" Liquidtight flexible metal conduit (LFMC)

1.981 sq in × 40 % = 0.7924 sq in allowed. ÷ 0.0211 sq in per wire = 37.55, so 37.

37 #10 THHN in 1-1/2" Liquidtight, drawn to scale

This pull in numbers

37 wires fill
39.4 % of 1-1/2" Liquidtight
Limit for three or more
40 %
For 38 or more
2" Liquidtight, up to 61
Pipe to wire diameter
9.68 to 1
In THW insulation
32 fit
In XHHW-2 insulation
32 fit

Before you pull 37

#10 THHN in other 1-1/2" conduit

#10 THHN in other Liquidtight sizes

Other wire sizes in 1-1/2" Liquidtight

Charts