ConduitCount

How many 500 kcmil THHN fit in 4" Liquidtight?

7500 kcmil THHN/THWN-2 wires in 4" Liquidtight flexible metal conduit (LFMC)

12.692 sq in × 40 % = 5.0768 sq in allowed. ÷ 0.7073 sq in per wire = 7.18, so 7.

7 500 kcmil THHN in 4" Liquidtight, drawn to scale

This pull in numbers

7 wires fill
39.0 % of 4" Liquidtight
Limit for three or more
40 %
For 8 or more
no bigger Liquidtight
Pipe to wire diameter
4.24 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

500 kcmil THHN in other 4" conduit

ConduitInside areaMost 500 kcmil THHN
Electrical metallic tubing14.7538
Intermediate metal conduit13.6317
Rigid metal conduit (RMC, GRC)12.8827
Rigid PVC conduit, Schedule 4012.5547
Rigid PVC conduit, Schedule 8011.2586
Flexible metal conduit (FMC, Greenfield)12.5667
Liquidtight flexible metal conduit (LFMC)12.6927

500 kcmil THHN in other Liquidtight sizes

Other wire sizes in 4" Liquidtight

Charts