ConduitCount

How many 500 kcmil THHN fit in 2-1/2" Liquidtight?

2500 kcmil THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 31 % = 1.5131 sq in allowed. ÷ 0.7073 sq in per wire = 2.14.

2 500 kcmil THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

2 wires fill
29.0 % of 2-1/2" Liquidtight
Limit for two
31 %
For 3 or more
3" Liquidtight, up to 4
Pipe to wire diameter
2.63 to 1
In THW insulation
1 fit
In XHHW-2 insulation
2 fit

Before you pull 2

500 kcmil THHN in other 2-1/2" conduit

ConduitInside areaMost 500 kcmil THHN
Electrical metallic tubing5.8583
Intermediate metal conduit5.1353
Rigid metal conduit (RMC, GRC)4.8662
Rigid PVC conduit, Schedule 404.6952
Rigid PVC conduit, Schedule 804.1191
Flexible metal conduit (FMC, Greenfield)4.9092
Liquidtight flexible metal conduit (LFMC)4.8812

500 kcmil THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts